Engineering Systems for Galleries


                                    James R. Briggs and Peter Smith






        All material objects deteriorate   possible to include windows provided   level track system has many uses.
       because they comprise various      these are located and constructed
       chemical components which may       realizing the implications of natural   Fire Control
       react with other components and     light variations, of both level and colour   We put this as the second priority but
       with the components of their       temperature, and its high ultra-violet   consider it of equal importance to lighting
       environment. The reaction or        content. The latter may be filtered out.   because a destroyed object is worthless
       deterioration rate depends on the   The filter should be in a permanent form   and the safety of people must be
       chemical components involved and    that will not deteriorate with time, and   paramount. The key to successful fire
       the quantity and quality of light and   the window size and location need to be   prevention is to start with a low fire
       heat energy present. If excessive   selected and controlled so that     risk, by excluding as much easily
       deterioration is to be avoided then   maximum internal illumination levels are   combustible material as possible, and
       it can be essential to control the   not exceeded and some form of automatic   then arranging for detection at the
       environment's chemical              blinds or shutters may be needed. It must   earliest possible moment. This is best
       components, such as sulphur dioxide   also be realized that windows are a great   done by an automatic detector system
       and water vapour, which may react   source of heat gain and loss and lead to a   supplemented by the ordinary 'break
       with the object, both chemically and   greater need for air conditioning or   glass' call points — which may be
       physically, and the light and heat   heating as well as being prone to   statutorily required anyway. Detection
       energy levels, particularly light.   condensation and, where not sealed, to   must of course be immediately and
       Also it is essential to have the lowest   the ingress of dirt. In any event an   effectively indicated and, when people are
       possible fire risk.                 artificial lighting system will be needed   present, a general alarm given. A fire bell
        In practical terms the factors     and luminaires designed for display are   system is probably adequate when staff
       that need to be considered are:     available in standard ranges, but can also   are present but direct indication to a
       the lighting (both natural and      be specially made. Suitable light sources   central building point and to the Fire
       artificial); fire control (ie       are fluorescent, tungsten filament and   Brigade is much to be preferred and, also,
       detection, indication, alarm and    tungsten halogen lamps. Mercury and   perhaps to a commercial control centre
       fighting); air condition (ie        sodium lamps are not satisfactory because   that would relay a signal in the event of a
       temperature, humidity and air       of their colour effects. Fluorescent lighting   malfunction. To avoid malfunctions at
       purity); security; communications   with 150o and 1800 nun tubes should be   times of emergency, as far as possible, the
       and emergency energy supply — and   used as much as possible, because the   wiring system should be arranged to be of
       for us this is the order of priority.   energy consumption is relatively low, and   the 'fail safe' type in which any departure
       For a new building the cost of      when used with correctly matched tubes,   from normal gives an indication of a fault
       providing engineering systems to    shielded with a diffuser to absorb UV   condition and thus be proof against
       give ideal protection, for all these   and to avoid glare, can supplement   equipment failure and interference.
       factors, can easily exceed 40% of the   natural lighting very well, as has been   Once a fire does start it is essential to
       total building cost and it is, therefore,   done at the National and Hayward   have, immediately to hand, equipment
       necessary carefully to consider the   Galleries in London. But, particularly   that will tackle the fire in the best way to
       degree of protection justified for   where there is no natural lighting, it is   reduce to the minimum damage caused
       each factor, and we have tried in this   difficult to use fluorescent lighting in an   by the fighting agent. This can range
       brief paper to set out some of the   aesthically pleasing way at the lower   from hand-held extinguishers to the
       main parameters.                    illumination levels. Where modelling is   final resort of the main water hoses of
                                           important, and for special effects, the   the Brigade, and, between these two
       Lighting                            less efficient tungsten filament lamp is   extremes, there are; first aid hose reels
         Since art is nothing if not seen,   probably best, because it is possible to   (which may deliver water or gas); local
       lighting is, for us, of primary     use different beam angles and projection   gas flooding; water sprinklers and
       importance and is needed both to    to obtain precise particular effects —  drenchers and building gas flooding
       illuminate exhibits and the public ways   although it is helpful to get computer   systems. It is our opinion that things
       through the building — care is needed   assistance with the calculations.   have gone sadly wrong if the Brigade
       to prevent conflict between the two   Dimming can be used for final     need to resort to their main hoses and
       functions and particularly to avoid   adjustment and it is worth knowing that   that the building equipment should
       pools of bright light against a dark back-  the lamp life can be increased from the   include `BCF' gas hand-held
       ground. Unfortunately the ideal levels   normal z000 hours up to 800o hours with   extinguishers as the best method of
       of light for visual comfort can be very   a io%voltage reduction. Dimmers   initial attack backed up by water hose
       damaging, particularly when there is an   should therefore be of the Thyristor   reels, since these are continuous and
       ultra-violet content and the effects   type and the electrical system must be   carefully used do not cause more damage
       depend on the illumination levels, time   arranged to accept the fourteen times   than they prevent. Perhaps other than in
       of exposure and the chemical        steady-state current that can occur on   public areas, CO2   gas flooding seems to
       composition of the object. Fabrics and   switch-on and may damage the   us to be highly desirable as it can be set
       paper, particularly with watercolour   dimmers. Voltage reduction does cause   to be automatic when there are no staff
       pigments, are very sensitive and for   an increase of the red content of the   present, when statistically, the time most
       these the illumination levels should not   light but this is not often significant.   fires start.
       exceed 150 lux (50 for watercolours etc.)   Tungsten halogen lamps cannot be
       with no ultra-violet component. For   dimmed and need careful installation to   Air condition
       maximum protection light should be   achieve a 2000 hour life but its small size   The air temperature, humidity and
       excluded as much as possible and, in   and high quality light-output make it   purity all have an effect on all objects, but
       extreme cases, time limiting may be   invaluable for accurate focusing and   some objects are more sensitive than
       needed ie 'push button to display'   projection over long distances. Below   others, and, from our study of the
       techniques. Most people would agree   30o watts the supply voltage must be   literature, we have concluded that it is
       that artificial lighting is a poor   reduced by a transformer. Flexibility of   change of the moisture content that is
       substitute for natural lighting and it is   lighting is the main need and a high    the most damaging, and this is constant